FR Engineering centre of fire robots technology
Fire robots and fire monitors
the basis for the modern
fire extinguishing
technologies

About production

The fire monitors meet the requirements of GOST R 51115-97 and TU-4854-003-16820082-2008, they classified in accordance with GOST R 51115-97:
LS – fire monitor
S – fixed
V – vehicle-mounted
P – portable, mobile
U – universal, a dispersed water or foam stream with adjustable angle
without index "U" - forming the straight stream of water and foam
D – remote-controlled
without index "D" - manually-operated
20-330 - flow rate of water and foam former solution, l/sec.

An example of description for a water/foam universal fixed remote-controlled fire monitor with the flow rate of 100 l/sec is given: LSD-S100U.

For articles made by «FR» Engineering Centre of Fire Robots Technology» in accordance with TU 4854-003-16820082 -2008 the additional index is given in the article type definition, which should be in the end of article type definition under GOST, after index U to classify:
1. Constructive modification of fire monitor:
U
– tube construction
Ul – with lower installation of monitor
Uul – with upper and lower (variable) installation of monitor
without index «D» - with upper installation of monitor
Ub – with ball-socket
2. Types of nozzles:
U
– with dispersed stream, universal (main modification)
without index U - with straight stream, conic
Ui – impact
Ue – with foam eductor
U – with automat nozzle
Ud – with deflector
3. Additional devices:
U – without additional devices
Uss – with shielding screen device
U – with oscillator
4. Extinguishing solution:
U
– water/foam (combined monitor)
Up – powder (powder monitor)

After definition of monitor type the information of equipment modification for the conditions of environment is given:
1. Climatic modification:
TC, T, UM - fire robots are produced in general industrial and marine modification
2. Protection type:
Ex
– explosion-proof, 1ExdIICT4 – type of 1ExdIICT4 explosion proof
IP55, IP65, IP66 - dust and moisture proof

Handline nozzles meet the requirements of GOST R 53331-2009 and TU 4854-004-16820082-08 and are classified in accordance with GOST 53331-2009:
RSKU - combined universal handline nozzles,
20, 50, 70 - swivel base
HP - high pressure
without HP index - normal pressure.

The following types of «FR» handline nozzles are produced:
RSKU-50, RSKU-70 - combined (water-foam) universal handline nozzles with adjusting of flow rate and angle of a dispersed stream, with swivel base 50 and 70.
RSKU-50e, RSKU-70e - the same, with educting of foam from baskpack, with possibility of immediate switching from water to foam and back, with swivel base 50 and 70.
RSKU-50a, RSKU-70a FIREMAN'S AUTOMAT® – automatic combined, universal handline nozzle, with manual and automatic adjustment of flow rate, adjustable stream spray angle, with swivel base 50 and 70, with flow rate from 2 up to 8 l/sec and from 4 up to 15 l/sec.
RSKU-50a «FLUSH» - automatic, combined, universal handline nozzle, with manual and automatic adjustment flow rate, adjustable stream spray angle, with swivel base 50, with flow rate from 2 up to 9 l/sec.
RSKU-20hp – high pressure universal handline nozzle with adjustable flow rate and stream angle, with shielding screen 120°.

Robotic fire suppression systems meet the requirement of GOST R 53326-2009 and TU-4854-005-16820082-2005, and consist of:
RFSS - robotic fire suppression system
2(32)FR - fire robots (FR) and as a component of RFSS,
LSD-S20(100)U - type of fire monitor, included in FR,
IR- with ignition detector device in IR-range,
IR-TV - with ignition detector device in IR-range and TV-camera.

Example of definition under GOST R 53326-2009 RFSS with 6 FR based on fire monitors (LSD) with flow rate 20 l/sec (20) with ignition detector device in IR-range (IR), TV-cameras (TV): RFSS-6FR-LSD-S20U-IR-TV.