Name of parameters
80 90 100
Flow rate of water (foam agent solution), l/s 80 90 100
Nominal pressure, MPa 0,8
Operating pressure range, MPa 0,4-1,0
Stream range (outermost) at nominal pressure, m, not less than::
- straight water stream 82 89 93
- dispersed (at a stream discharge angle of 30°) 56 61 63
- straight foam 69 75 80
Oscillation angles, ° 30±5,70±5, 110±5
Fire monitor displacement speed at oscillation, °/sec 2-6
Working area of monitor rotation, degrees:
- vertical up +90 to -45
- horizontal 360
Weight, kg, not more than -
Useful information
Certificates All certificates

Products: Combined universal fire monitors, are manufactured in accordance with the Technical specifications TU 4854-003-16820082-2008 with amendment 7.

Certificate validity period: from 24.11.2021 till  24.11.2026

 