Fire monitor water/foam, universal, fixed, with remote control/, with flow rate of 70, 80, 90, 100, 125 l/s, of tube construction. 

The fire monitor is applied for formation of extinguishing solution streams with adjustable spray angle from a straight stream to a dispersed at 90°.

The fire monitor is used in fire hazardous zones for fire suppression, cooling of buildings and technological structures, precipitation of poisoned or radioactive gases, fumes and dusts.

Fire monitors are produced in a climatic category in accordance with GOST 15150: UKhL 1.1 UKhL 1, U 1, OM 1. Fire monitors are produced in accordance with the requirements of Technical Specifications ТU 4854-003-16820082-2008 and TR EAEU 043/2017.

More
LSD-S100(70,80,90,125)U
Features
Name of parameters
70 80 90 100 125
Nominal pressure, MPa 0,8
Operating pressure range, MPa 0,4-1,0
Flow rate of water (foam agent solution), l/s 70 80 90 100 125
Stream range (outermost) at nominal pressure, m, not less than::
- straight water stream 83 87 95 100 105
- dispersed (at a stream discharge angle of 30°) 51 53 58 61 65
- straight foam 70 74 81 85 86
Angle range of a dispersed water stream, degrees 0-90
Working area of monitor rotation, degrees:
- vertical up +90 to -45
- horizontal 345
Displacement speed, degree/s:
- sprinkling / targeting 3-6 / 8-10
Electric supply voltage, V 24
Weight, kg, not more than 60
Useful information
Certificates All certificates

Products: fire monitors are manufactured in accordance with the Technical specifications TU 28.29.22-025-16820082-2026.

The products comply with the requirements of the Technical regulations TR EAEU 043/2017 "On the requirements for fire safety and fire extinguishing equipment".

Certificate validity period: from 09.10.2026 till 08.10.2031

Your privacy is our concern This site uses cookies. You consent to their use by continuing using this site.
Agree