Description
Description

LSD-S20Ue - fixed fire monitor, with remote control, with flow rate of 20  l/s, with foam eductor nozzle.

The fire monitor is applied for formation of extinguishing agent dispersed streams with adjustable spray angle from a straight stream to a dispersed at 90°. Fire monitors are used for fire suppression, cooling of buildings and technological structures, precipitation of poisoned or radioactive gases, fumes and dusts. 

Features:

Fire monitors with foam eductor nozzles enables to quickly make a foam stream. Water is supplied to the fire monitor with a foam eductor nozzle through pipes or hoses. The dosed supply of foam agent into the water is carried out from a separate container through a separate vacuum hose by an eductor located in the nozzle.  A foam stream is formed at the outlet of the monitor, and when the foam agent supply is shut off, a straight or dispersed water stream is formed. Fire monitors with foam eductor nozzles enable not to use expensive foam dosing pump stations and are effective for obtaining high-quality foam for the protection of oil and gas facilities.

Fire monitors are produced in accordance with the requirements of Technical Specifications ТU 4854-003-16820082-2008,  TR EAEU 043/2017, GOST R 51115-97, GOST 34778-2021.

 

More
LSD-S20Ue
Features
Name of parameters
20
Nominal pressure, MPa 0,8
Operating pressure range, MPa 0,4-1,0
Flow rate of water (foam agent solution), l/s 20
Stream range (outermost) at nominal pressure, m, not less than::
- straight water stream 53
- dispersed (at a stream discharge angle of 30°) 33
- straight foam 46
Angle range of a dispersed water stream, degrees 0-90
Concentration of foam former's water solution, % 3±0,6; 6±1,2
Working area of monitor rotation, degrees:
- vertical up +90 to -45
- horizontal 345
Electric supply voltage, V 24
Displacement speed, degree/s:
- sprinkling / targeting 3-6 / 8-10
Weight, kg, not more than -
Certificates All certificates

Products: Water-foam fire monitors, universal, with manual and remote control, stationary, portable, trailer-mounted (including construction versions: low - "n", ball-socket - "b", explosion-proof - "Ex") of LS, LSD types, are manufactured in accordance with the Technical specifications TU 4854-003-16820082-2008 with amendment 7.

The products comply with the requirements of the Technical regulations TR EAEU 043/2017 "On the requirements for fire safety and fire extinguishing equipment".

Certificate validity period: from 06.07.2021 till 06.06.2026.