Description
Description

Fire monitor, water-foam, universal, stationary, with flow rate of of water or foam former solution 15, 20, 25 l/s , with a heat shielding screen (hereinafter referred to as LS).

Fire monitors are designed to form jets of fire extinguishing agent with a variable spray angle from a straight jet to a dispersed jet with a spray angle of 90 °, heat shielding screens are designed for long-term protection of the operator of the fire monitor from high-intensity thermal  radiation during a fire.

LS is used for fire extinguishing, building and technological structures cooling, clouds of poisoned or radioactive gases, fumes and dusts precipitation. LS is produced under TU 4854-003-16820082-2008, TU 28.99.39-016-16820082-2019  and GOST R 51115-97.

Abbreviations: fire monitor – LS, stationary – S, with flow rate of water or foam former solution 15, 20, 25 l/s – 20 (15,25), with universal nozzle – U.

More
LS-S20(15,25)Ute
Features
Name of parameters
15 20 25
Nominal pressure, MPa 0,8
Operating pressure range, MPa -
Flow rate of water (foam agent solution), l/s 15 20 25
:
straight water stream 50 55 59
- dispersed (at a stream discharge angle of 30°) 31 34 35
- straight foam 44 47 49
Foam expansion ratio, not less than 7
Working area of monitor rotation, degrees:
- vertical от -15 до +75
- horizontal 360
Сlimatic category in accordance with GOST 15150-69 UKhL 1
:
70
40