Description
Description

Fire monitor water/foam, universal, fixed, with manual control, with flow rate of 40, 20, 30 l/s, of tube construction, with with quick-release connection. 

The fire monitor is applied for formation of extinguishing solution streams with adjustable spray angle from a straight stream to a dispersed at 90°.

The fire monitor is used in fire hazardous zones for fire suppression, cooling of buildings and technological structures, precipitation of poisoned or radioactive gases, fumes and dusts.

Fire monitors are produced in accordance with the requirements of Technical Specifications ТU 28.29.22-025-16820082-2026,  TR EAEU 043/2017,  GOST 34778-2021.

More
LS-S40(20,30)U
Features
Name of parameters
20 30 40
Nominal pressure, MPa 0,8
Operating pressure range, MPa 0,4-1,0
Flow rate of water (foam agent solution), l/s 25 30 40
Stream range (outermost) at nominal pressure, m, not less than::
- straight water stream 55 62 65
- dispersed (at a stream discharge angle of 30°) 34 38 42
- straight foam 47 53 55
Angle range of a dispersed water stream, degrees 0-90
Working area of monitor rotation, degrees:
- horizontal 360
- vertical up +90 to -45
Weight, kg, not more than 17