Description
Description

Fire monitor water/foam, universal, fixed, with manual control, with flow rate of 80. 90 or 100 l/s, with oscillator, of tube construction.

The fire monitor is applied for formation of straight and dispersed streams of fire extinguishing agent with adjustable spray angle from a straight stream to a dispersed at 90°, with an option of monitor travel (oscillation) within a required sector using the energy of water flow supplied to the monitor.

The fire monitors with oscillators are used for making of water shield or cooling of huge areas, for example tank farms, oil-filled power transforming substations.

Fire monitors are produced in a climatic category in accordance with GOST 15150: UHL 1.1 UHL 1, U 1, OM 1. Fire monitors are produced in accordance with the requirements of Technical Specifications ТU 4854-003-16820082-2008 and TR EAEU 043/2017.

More
LS-S100(80,90)Uo
Features
Name of parameters
80 90 100
Flow rate of water (foam agent solution), l/s 80 90 100
Nominal pressure, MPa 0,8
Operating pressure range, MPa 0,4-1,0
Stream range (outermost) at nominal pressure, m, not less than::
- straight water stream 82 89 93
- dispersed (at a stream discharge angle of 30°) 56 61 63
- straight foam 69 75 80
Oscillation angles, ° 30±5,70±5, 110±5
Fire monitor displacement speed at oscillation, °/sec 2-6
Working area of monitor rotation, degrees:
- vertical up +90 to -45
- horizontal 360
Weight, kg, not more than 60
Useful information
Certificates All certificates

Products: Combined universal fire monitors, are manufactured in accordance with the Technical specifications TU 4854-003-16820082-2008 with amendment 7.

Certificate validity period: from 24.11.2021 till  24.11.2026

 