Fire monitor fixed, with manual conrol, with flow range of 40 l/s, with foam eductor nozzle.

The fire monitor is applied for formation of extinguishing agent dispersed streams with adjustable spray angle from a straight stream to a dispersed at 90°. Fire monitors are used for fire suppression, cooling of buildings and technological structures, precipitation of poisoned or radioactive gases, fumes and dusts.

Feauters:

  • Fire monitors with foam eductor nozzles enables to quickly make a foam stream. Water is supplied to the fire monitor with a foam eductor nozzle through pipes or hoses. The dosed supply of foam agent into the water is carried out from a separate container through a separate vacuum hose by an eductor located in the nozzle. A foam stream is formed at the outlet of the monitor, and when the foam agent supply is shut off, a straight or dispersed water stream is formed. Fire monitors with foam eductor nozzles enable not to use expensive foam dosing pump stations and are effective for obtaining high-quality foam for the protection of oil and gas facilities.

Fire monitors are produced in accordance with the requirements of Technical Specifications ТU 4854-003-16820082-2008,  TR EAEU 043/2017, GOST R 51115-97, GOST 34778-2021.

More
LS-S40Ue
Features
Name of parameters
40
Nominal pressure, MPa 0,8
Operating pressure range, MPa 0,4-1,0
Flow rate of water (foam agent solution), l/s 40
Stream range (outermost) at nominal pressure, m, not less than::
- straight water stream 63
- dispersed (at a stream discharge angle of 30°) 41
- straight foam 53
Angle range of a dispersed water stream, degrees 0-90
Concentration of foam former's water solution, % 3±0,6; 6±1,2
Working area of monitor rotation, degrees:
- vertical up +90 to -45
- horizontal 360
Weight, kg, not more than -