Description
Description

Fire monitor water/foam, universal, fixed, with manual control, with flow rate of 20, 30, 40 l/s, with oscillator. 

Fire monitors with oscillators are applied for formation of straight and dispersed streams of fire extinguishing agent with adjustable spray angle from a straight stream to a dispersed at 90°, with an option of monitor travel (oscillation) within a required sector using the energy of water flow supplied to the monitor.

There are used for making of water shield or cooling of huge areas, for example tank farms, oil-filled power transforming substations.

Fire monitors are produced in a climatic category in accordance with GOST 15150: UHL 1.1 , U 1, OM 1.

Fire monitors are produced in accordance with the requirements of Technical Specifications ТU 4854-003-16820082-2008 and TR EAEU 043/2017.

More
LS-S40(20,30)Uo
Features
Name of parameters
20 30 40
Flow rate of water (foam agent solution), l/s 20 30 40
Nominal pressure, MPa 0,8
Operating pressure range, MPa 0,4-1,0
Stream range (outermost) at nominal pressure, m, not less than::
- straight water stream 50 55 62
- dispersed (at a stream discharge angle of 30°) 30 34 40
- straight foam 43 47 50
Oscillation angles, ° 30±5,70±5, 110±5
Fire monitor displacement speed at oscillation, °/sec 2-6
Working area of monitor rotation, degrees:
- vertical up +90 to -45
- horizontal 360
Weight, kg, not more than -
Useful information