Description

Fire monitor water/foam, fixed, universal, with manual control, with flow rate of 200, 250, 330 l/s, with cone nozzle, of tube construction. 

The fire monitor with cone nozzle is applied for formation straight streams of extinguishing solution. 

The fire monitor is used in fire hazardous zones for fire suppression, cooling of buildings and technological structures, precipitation of poisoned or radioactive gases, fumes and dusts.

Fire monitors are produced in accordance with the requirements of Technical Specifications ТU 4854-003-16820082-2008 and TR EAEU 043/2017.

 

More
LS-S330(200,250)
Features
Name of parameters
200 250 330
Nominal pressure, MPa 0,8
Operating pressure range, MPa -
Flow rate of water (foam agent solution), l/s 200 250 330
Stream range (outermost) at nominal pressure, m, not less than::
- straight water stream 120 140 150
- straight foam 105 125 135
Angle range of a dispersed water stream, degrees 0-90
:
up -15 to +75
360
Сlimatic category in accordance with GOST 15150-69 U1, UKhL 1.1
120
Weight, kg, not more than 300
Useful information
Certificates All certificates

Products: fire monitors LS-S330(200,250)U, LS-S330(200,250), LS-V330(200,250), LS-V330(200,250)У, are manufactured in accordance with the Technical specifications TU 28.99.22-020-16820082-2023.

Certificate validity period: from 15.09.2023 till 14.09.2028.

 